MultiCrafTest Electrical Maintenance

The electrical side of the Ramsay MultiCrafTest: AC/DC theory, motors and controls, ladder diagrams and PLC signals, with formulas and worked examples.

Practicing for the Ramsay MultiCrafTest? Take the free practice test: 14 questions, no account needed.

Three of the seven MultiCrafTest craft areas are electrical: AC/DC theory and electrical maintenance; motors, control circuits and print reading; and digital electronics, PLCs and test instruments. This guide covers the formulas and the reading skills those questions use. Every example is original.

AC/DC theory and electrical maintenance

Ohm's law. Volts = amps × ohms. A 40 Ω heater on 120 V draws 120 ÷ 40 = 3 A.

Series and parallel. In series, resistances add: 6 Ω and 12 Ω make 18 Ω. In parallel, use product over sum: 6 × 12 ÷ (6 + 12) = 4 Ω. The parallel result is always less than the smallest resistor.

Power. DC power = volts × amps. Single-phase AC real power = volts × amps × power factor: 120 V × 8 A × 0.85 = 816 W. Volts × amps alone is apparent power, in VA.

Transformers. Voltage follows the turns ratio. A 4:1 step-down transformer with 480 V on the primary gives 120 V on the secondary.

Safe practice. Before work, isolate, lock out and prove the circuit dead with a tester you've checked on a known live source. An insulation tester (megohmmeter) checks insulation; it isn't for live circuits.

Motors, controls and print reading

Synchronous speed. Synchronous speed = 120 × frequency ÷ poles. A 10-pole motor on 60 Hz has a field speed of 120 × 60 ÷ 10 = 720 rpm. The rotor turns a little slower under load; that difference is slip.

Slip. Slip = (synchronous speed − shaft speed) ÷ synchronous speed. That motor running at 702 rpm has (720 − 702) ÷ 720 = 2.5% slip.

Three-wire control. A START button momentarily energizes the starter coil, and a normally open auxiliary contact in parallel with START (the seal-in contact) keeps it energized. A normally closed STOP button and the overload contact sit in series. Two consequences come up often:

  • if the motor stops when START is released, suspect the seal-in path;
  • after a power loss, a three-wire circuit stays off until someone presses START again (no-voltage release).
A ladder diagram between rails L1 and L2. One rung runs from L1 through a normally closed STOP pushbutton, a normally open START pushbutton, the starter coil M and a normally closed overload contact OL to L2. A branch around the START button holds a normally open contact M, labeled seal-in contact.
Three-wire control: the seal-in contact M, in parallel with START, keeps the coil energized after START is released.

Reading a ladder rung. Power flows from the left rail to the right through the contacts to the coil.

On the rung Means
Contacts in series AND
Contacts on parallel branches OR
Normally closed contact NOT (it conducts while its input is off)

So a normally open contact X in series with a normally closed contact Y energizes the coil when X AND NOT Y. Put the same two contacts on parallel branches and it's X OR NOT Y.

Two ladder rungs between rails L1 and L2, each ending at coil CR1. In the first, a normally open contact X and a normally closed contact Y are in series. In the second, the same two contacts sit on parallel branches.
The same two contacts in series (AND) and on parallel branches (OR).

Electronics, PLCs and test instruments

Logic gates. AND is true only when both inputs are true; OR when either is; XOR when exactly one is. A small circle (bubble) on the output inverts it: AND becomes NAND, OR becomes NOR, XOR becomes XNOR.

4–20 mA scaling. 4 mA is the bottom of the range and 20 mA the top, a 16 mA span. A 0–100 psi transmitter sending 8 mA reads (8 − 4) ÷ 16 × 100 = 25 psi.

Two matched scales. The signal scale runs from 4 mA to 20 mA, a 16 mA span; the reading scale below it runs from 0 psi to 100 psi. A teal mark at 8 mA on the signal scale is carried straight down to 25 psi on the reading scale.
8 mA is a quarter of the way up the 16 mA span, so it reads a quarter of 100 psi.

1–5 V scaling works the same way: 1 V is 0% and 5 V is 100%, so 2 V is 25%.

Analog-to-digital converters. An n-bit converter has 2ⁿ codes, from 0 to 2ⁿ − 1. A 14-bit converter has 16,384 codes, the largest being 16,383.

Duty cycle. Time on ÷ period. An output on for 6 ms of every 24 ms has a 25% duty cycle.

PLC timing. Total delay adds up: a 4-second permissive wait followed by a 7-second on-delay timer gives 11 seconds before the output can come on.

Troubleshooting a PLC input. If the field device is switching but the input stays off, measure at the PLC terminal. Voltage at the device but none at the terminal means an open wire or loose connection between them; voltage at the terminal with the input still off points to the input card or its configuration.

How to work fast

  • For a calculation, name the formula, then put the numbers in.
  • For a ladder or gate question, write the expression before you look at the choices.
  • For a fault question, follow the signal or the current path and find where the evidence changes.

Practice

The free MultiCrafTest practice test has two questions from each craft area. Each of our 20 full practice tests mixes 60 questions across all seven areas, with a worked explanation for every one. For the mechanical areas, see the mechanical maintenance guide.

Free to share: you may copy and share this guide unchanged, for non-commercial purposes such as teaching and study, if you credit ExamVanta and link to this page. It's licensed under CC BY-NC-ND 4.0. Material from other sources quoted or shown in it, such as official text or chart excerpts, keeps its own terms.