MultiCrafTest PLCs, Electronics and Test Instruments Guide

PLCs, electronics and test instruments for the Ramsay MultiCrafTest: PLC scan and I/O, 4–20 mA scaling, sensors, safe meter use and logic gates, with worked examples.

Practicing for the Ramsay MultiCrafTest? Take the free practice test: 14 questions, no account needed.

Ramsay's MultiCrafTest product page lists "Digital Electronics, Power Supplies, Computers & PLC, and Test Instruments" as one of its seven categories. In your ExamVanta results, this area is called Electronics, PLCs and test instruments.

This guide goes deeper than the electrical maintenance overview. It covers how a PLC reads and writes field devices, how to scale and check a 4–20 mA loop, how common sensors work, how to use a meter safely, and the electronics behind it all. The five worked examples are original.

PLC inputs, outputs and the scan

A PLC works in a repeating scan:

  1. Read every input and store the states in the input image table.
  2. Solve the program, rung by rung, top to bottom and left to right.
  3. Write the results to the outputs.
  4. Handle communications and self-checks, then start again.

Because inputs are read once per scan, a very short pulse can be missed. As a safe rule, a signal has to stay on for longer than one scan plus the input card's filter delay. On a PLC with a 15 ms scan and a 2 ms input filter, that's more than 15 + 2 = 17 ms. A part that blocks a photoeye for only 8 ms can be missed. The fix is a high-speed counter, an interrupt input or a sensor with an off-delay to stretch the pulse. If a scan ever takes longer than the processor's limit, the watchdog faults the PLC and its outputs go to their fault state, usually off.

Discrete inputs are sinking or sourcing:

  • A PNP (sourcing) sensor switches +24 V to the input, so it needs a sinking input card, whose common goes to 0 V.
  • An NPN (sinking) sensor switches the input to 0 V, so it needs a sourcing input card.

Discrete outputs come in three main kinds. Relay outputs switch AC or DC but wear and switch slowly. Transistor outputs switch DC quickly. Triac outputs switch AC and leak a small current when off, which can keep a small relay pulled in or a pilot light glowing.

Status lights help you split a fault. An input light on means the card sees voltage. An output light on means the processor turned the output on, not that the load has power: a blown output fuse or open field wire leaves the light on and the load dead.

Ladder logic contacts, timers and fail-safe wiring

In a PLC program, a contact instruction looks at a bit, not at a physical contact:

Instruction Allen-Bradley name True when the bit is
Normally open contact, drawn ] [ XIC, examine if closed 1
Normally closed contact, drawn ]/[ XIO, examine if open 0

This trips people up. A STOP button is wired normally closed to its input, so its bit is 1 while nobody touches it. The program therefore examines it with a normally open (XIC) instruction in series with the run rung. Press STOP, or let the wire break, and the bit goes to 0 and the motor stops. That's fail-safe wiring: a broken wire acts like a stop, not like a start.

The seal-in works as it does in hard wiring: the output's own bit, examined with a normally open instruction, sits in parallel with START. Latch and unlatch outputs (OTL and OTU) hold their state until unlatched, even through a power cycle, so use them with care on machine motion. Emergency stops and guard circuits belong in a hardwired safety relay or a safety-rated controller, not in standard PLC logic alone.

Timers count in time-base units. An on-delay timer (TON) times while its rung is true and resets when it goes false. An off-delay timer (TOF) times after its rung goes false. A retentive timer (RTO) keeps its count when the rung goes false and needs a reset instruction. Counters (CTU, CTD) count false-to-true transitions of their rung.

4–20 mA loops, scaling and live zero

A 4–20 mA transmitter sends 4 mA at the bottom of its range (the lower range value) and 20 mA at the top (the upper range value). The span is 16 mA. Because the bottom is 4 mA and not 0 mA, the signal has a live zero: 0 mA means a fault, such as an open loop or lost power, never a process value of zero. Many transmitters follow the NAMUR NE 43 convention of driving the signal to 3.6 mA or below, or 21 mA or above, to report a failure.

To convert current to a process value:

value = lower range value + (mA − 4) ÷ 16 × (upper range value − lower range value)

To convert a process value to current:

mA = 4 + 16 × (value − lower range value) ÷ (upper range value − lower range value)

Worked example 1: a range that doesn't start at zero. A temperature transmitter is ranged 50 to 250 °F and sends 14 mA. Fraction of span = (14 − 4) ÷ 16 = 10 ÷ 16 = 0.625. The range is 250 − 50 = 200 °F, so the value is 50 + 0.625 × 200 = 50 + 125 = 175 °F. Check it backward: 4 + 16 × (175 − 50) ÷ 200 = 4 + 16 × 0.625 = 14 mA.

Worked example 2: the current to expect, and the voltage it makes. A transmitter is ranged −20 to 100 °C. At 0 °C it should send 4 + 16 × (0 − (−20)) ÷ 120 = 4 + 16 × 0.1667 ≈ 6.67 mA. An input that reads current as voltage across a 250 Ω resistor turns 4–20 mA into 1–5 V, so this input sees 0.006667 A × 250 Ω ≈ 1.667 V. Check: (1.667 − 1) ÷ 4 ≈ 0.1667 of span, and 0.1667 × 120 − 20 ≈ 0 °C.

In a two-wire loop, a 24 V DC supply powers the loop and the transmitter sets the current. Every device in the loop drops voltage, so the loop has a resistance limit:

maximum loop resistance = (supply voltage − transmitter's minimum operating voltage) ÷ 0.020 A

Worked example 3: loop resistance budget. The supply is 24 V and the transmitter needs at least 12 V at its terminals. Maximum loop resistance = (24 − 12) ÷ 0.020 = 12 ÷ 0.020 = 600 Ω. The loop has a 250 Ω PLC input, a 100 Ω panel indicator and 40 Ω of cable: 250 + 100 + 40 = 390 Ω, which fits. Add a second 250 Ω recorder input and it's 640 Ω. Now the transmitter can't reach 20 mA, and the top of the range reads low.

Measure loop current with a clamp-on milliamp meter, at the transmitter's test terminals, or as voltage across a known resistor, so you don't open a live loop. A signal correct at the transmitter but wrong in the PLC points to scaling, configuration or wiring at the card. A value that jumps when a nearby drive runs points to cable routing, shielding or grounding.

Sensors: proximity, photoelectric and temperature

  • Inductive proximity sensors detect metal. Sensing distance is longest for steel and shorter for aluminum, brass and copper.
  • Capacitive proximity sensors also detect nonmetals such as plastic, liquid or grain, and usually have a sensitivity adjustment.
  • Photoelectric sensors come as through-beam (separate emitter and receiver, longest range and most dependable), retroreflective (bounces off a reflector; a polarized type ignores shiny targets) and diffuse (bounces off the target itself, so color and finish matter). Light-operate turns the output on when the receiver sees light; dark-operate when it doesn't.
  • On most three-wire DC sensors, brown is +, blue is 0 V and black is the output. Two-wire sensors leak a little current when off, which can confuse some inputs.

An RTD is a resistor whose value rises with temperature. A Pt100 element is 100 Ω at 0 °C and rises by about 0.385 Ω per °C.

Worked example 4: reading an RTD. You measure 119.4 Ω on a Pt100. Temperature ≈ (119.4 − 100) ÷ 0.385 = 19.4 ÷ 0.385 ≈ 50 °C. The standard table gives 119.40 Ω at exactly 50 °C, so the straight-line shortcut is close over 0 to 100 °C. Lead resistance adds error on a two-wire hookup: 1 Ω of total lead resistance reads as about 1 ÷ 0.385 ≈ 2.6 °C too hot. A three-wire connection compensates for the leads, and a four-wire connection removes their effect.

A thermocouple makes a small voltage from the temperature difference between its measuring junction and its reference (cold) junction, which the instrument compensates for. Use extension wire of the same type, and keep polarity right: in the US color code, the red lead is negative. Reversed leads make the reading move the wrong way as the process heats.

Test instruments and meter safety

Choose a meter rated for where you'll use it. Measurement categories describe how big a voltage transient the meter can survive:

Category Where it applies
CAT II equipment that plugs into a receptacle
CAT III distribution panels, feeders, motors and fixed equipment in the building
CAT IV the origin of the installation: service entrance, utility meter, outdoor lines

The meter, leads and probes all need the rating, and the lowest of them sets the rating of the set. A CAT III or CAT IV meter is the usual choice for industrial work.

  • Test before touch. Check your tester on a known live source, test the circuit phase to phase and phase to ground, then check the tester on the known source again (live-dead-live).
  • Voltage in parallel, current in series. In current mode the meter is nearly a short. Placed across a voltage source, it blows its fuse or worse. Replace meter fuses only with the specified high-energy type.
  • Clamp meters measure current around one conductor. Clamp a whole cable and the currents cancel to near zero. To read a small current, loop the conductor through the jaw: five turns reading 3.0 A means 3.0 ÷ 5 = 0.6 A in the wire.
  • True-RMS meters read distorted waveforms, such as drive outputs and electronic loads, correctly. Some meters add a low-pass filter for VFD outputs.
  • A low-impedance (LoZ) setting drains ghost voltage, the induced reading on an open or disconnected conductor.
  • Measure resistance, continuity and diodes only on de-energized circuits, with capacitors discharged.

The insulation tester (megohmmeter) is covered in the AC/DC theory guide.

Electronics: diodes, power supplies, transistors and logic gates

A silicon diode conducts in one direction with a forward drop of about 0.6 to 0.7 V. On a meter's diode test, a good diode reads about that one way and OL the other. A short reads near zero both ways; an open reads OL both ways. A flyback diode across a DC coil, cathode to the positive side, clamps the voltage spike when the coil switches off.

A DC power supply rectifies, filters and usually regulates. A bridge rectifier fed from a 24 V AC winding charges its filter capacitor to about 24 × 1.414 − 2 × 0.7 ≈ 32.5 V at light load. On many meters, the AC volts range on a DC output shows the ripple. Excess ripple suggests a failing filter capacitor. A 24 V supply that sags under load is often overloaded.

A transistor used as a switch is driven fully off (cutoff) or fully on (saturation). For a bipolar transistor, give it enough base current to saturate. A common design rule is a base current of one tenth of the collector current.

Worked example 5: a transistor driving a relay. A 5 V logic output switches a 24 V relay coil of 480 Ω through an NPN transistor. Coil current ≈ 24 ÷ 480 = 0.05 A = 50 mA, ignoring the transistor's small saturation voltage. Base current = 50 ÷ 10 = 5 mA. The base resistor drops 5 − 0.7 = 4.3 V, so it's 4.3 ÷ 0.005 = 860 Ω. Choose the next standard value down, 820 Ω, giving 4.3 ÷ 820 ≈ 5.2 mA. Add a flyback diode across the coil.

Logic gates follow these truth tables (1 is true or high):

A B AND OR NAND NOR XOR XNOR
0 0 0 0 1 1 0 1
0 1 0 1 1 0 1 0
1 0 0 1 1 0 1 0
1 1 1 1 0 0 0 1

De Morgan's laws link them: NOT (A AND B) = NOT A OR NOT B, and NOT (A OR B) = NOT A AND NOT B. A pull-up resistor holds an input high until a switch to 0 V pulls it low; without it, an open input floats and reads at random.

Practice that matches the test

For signal questions, write the scaling formula with the range in it before you look at the choices. For fault questions, find the point where the signal stops matching what it should be. For motor circuits and ladder prints, see the motors, controls and print reading guide. For a full plan, read how to prepare for the Ramsay MultiCrafTest.

The free MultiCrafTest practice test has two questions from each craft area. Our 20 full Ramsay MultiCrafTest practice tests mix 60 original questions across all seven areas, with a worked explanation for every one and your score for each area.

Watch the video lesson

Free to share: you may copy and share this guide unchanged, for non-commercial purposes such as teaching and study, if you credit ExamVanta and link to this page. It's licensed under CC BY-NC-ND 4.0. Material from other sources quoted or shown in it, such as official text or chart excerpts, keeps its own terms.