MultiCrafTest Motors and Controls
Motors, controls and print reading for the Ramsay MultiCrafTest: motor speed and slip, starters, seal-in, reversing, jog, VFDs and ladder prints, with worked examples.
Practicing for the Ramsay MultiCrafTest? Take the free practice test: 14 questions, no account needed.
Ramsay's MultiCrafTest product page lists "Motors, Control Circuits, and Schematics & Print Reading" as one of its seven categories. In your ExamVanta results, this area is called Motors, controls and print reading.
This guide goes deeper than the electrical maintenance overview. It covers the motor formulas a journey-level electrician or multicraft technician uses, how starters and control circuits behave, and how to read a ladder print to find a fault. The five worked examples are original.
Three-phase induction motors: speed and slip
A three-phase stator sets up a magnetic field that rotates at synchronous speed:
synchronous speed (rpm) = 120 × frequency (Hz) ÷ number of poles
The rotor of an induction motor always turns a little slower than the field. That difference is slip, and it's what induces current in the rotor bars so the motor can make torque. Slip rises as the load rises; an unloaded motor runs very close to synchronous speed.
slip (%) = (synchronous speed − shaft speed) ÷ synchronous speed × 100
| Poles | Synchronous speed at 60 Hz | Typical full-load nameplate speed |
|---|---|---|
| 2 | 3,600 rpm | about 3,450 to 3,550 rpm |
| 4 | 1,800 rpm | about 1,725 to 1,780 rpm |
| 6 | 1,200 rpm | about 1,140 to 1,180 rpm |
| 8 | 900 rpm | about 850 to 885 rpm |
A nameplate speed tells you the pole count, because full-load speed is always a little below synchronous speed.
Worked example 1: poles and slip from a nameplate. A 60 Hz motor's nameplate says 1,164 rpm. The nearest synchronous speed above 1,164 is 1,200 rpm, so it's a 6-pole motor (120 × 60 ÷ 6 = 1,200). Slip at full load is (1,200 − 1,164) ÷ 1,200 = 36 ÷ 1,200 = 0.03, or 3%. Check it the other way: 1,200 × (1 − 0.03) = 1,164 rpm.
A few more facts that come up in fault questions:
- Direction. Swapping any two of the three supply leads reverses rotation.
- Starting current. Started across the line, a motor draws several times its full-load current, often around six times, until it comes up to speed.
- Single phasing. If one phase opens while a motor is running, it may keep turning but draws more current on the two remaining lines and overheats. If a phase is open at start, the motor hums and won't turn. The overload relay should trip.
- Power factor. A lightly loaded induction motor has a low power factor. It improves as the motor approaches full load.
Starters, overloads and three-wire control
A magnetic motor starter is a contactor plus an overload relay. The contactor's main poles switch the motor. The overload relay measures motor current and, after a sustained overload, opens a normally closed contact in the control circuit, which drops out the coil. It doesn't open the power circuit itself, and it isn't short-circuit protection: that comes from the fuses or breaker ahead of the starter.
Overloads are set from the motor's nameplate full-load amps and the overload maker's instructions. The trip class is the longest time, in seconds, the relay takes to trip at 600% of its setting: a Class 10 relay trips within 10 seconds at six times its setting, a Class 20 within 20.
Three-wire control uses a normally closed STOP button, a normally open START button and a seal-in (holding) contact, a normally open auxiliary contact on the starter wired in parallel with START. Press START, the coil pulls in, the seal-in contact closes, and the coil stays energized after you let go. Press STOP, or let the overload trip, and the coil drops out.
After a power loss, the seal-in contact opens and the motor stays off until someone presses START. This is called low-voltage protection (some texts say no-voltage protection). A two-wire control, such as a float switch or thermostat wired straight to the coil, gives low-voltage release instead: the motor restarts by itself when power returns.
For more than one control station, wire all the STOP buttons in series and all the START buttons in parallel. Any STOP then breaks the circuit, and any START can energize it.
| Symptom | Where to look first |
|---|---|
| Motor runs only while START is held | the seal-in contact or its wiring |
| Nothing happens at START, control power present | STOP chain, overload contact, START contact, coil |
| Contactor hums or chatters | low control voltage, dirty pole faces, a broken shading coil on an AC magnet |
| Overload trips repeatedly | running current against nameplate, mechanical binding, low or unbalanced voltage, a lost phase |
Never just reset a tripped overload and walk away. Find out why it tripped.
Worked example 2: voltage unbalance. You measure 460 V, 467 V and 450 V line to line at a motor. The average is (460 + 467 + 450) ÷ 3 = 1,377 ÷ 3 = 459 V. The largest deviation from the average is 459 − 450 = 9 V. Percent unbalance = 9 ÷ 459 × 100 ≈ 2.0%. Check: 459 × 0.0196 ≈ 9 V. NEMA's motor standard calls for derating a motor above 1% voltage unbalance and advises against running it above 5%. The current unbalance will be several times larger than the voltage unbalance, so a 2% supply unbalance is worth tracing to its cause.
Reversing, interlocks and jog circuits
A reversing starter has two contactors, forward (F) and reverse (R). The reverse contactor swaps two of the lines to the motor, usually L1 and L3. If both closed at once, they would short two phases together, so the circuit is interlocked three ways:
- Mechanical interlock: a bar or lever between the two contactors physically stops both closing.
- Auxiliary contact interlock: a normally closed contact of R is wired in series with the F coil, and a normally closed contact of F in series with the R coil.
- Pushbutton interlock: double-circuit FORWARD and REVERSE buttons, where the normally closed half of each opens the other direction's circuit.
Reversing a motor at full speed (plugging) draws heavy current and stresses the drive train. Many circuits require STOP first, a time delay, or a zero-speed switch before the opposite direction can start.
Jog (inching) runs the motor only while the button is held. The trick is to stop the seal-in from holding the coil. A double-circuit JOG button does it by putting its normally closed contact in series with the seal-in contact while its normally open contact energizes the coil. If you release the button quickly, the normally closed contact can reclose before the seal-in contact opens, and the motor may seal in and keep running. A RUN/JOG selector switch that opens the seal-in path, or a separate jog control relay, avoids that race.
Control transformers and VFDs
A control transformer usually supplies the coils and pilot devices, stepping line voltage such as 480 V down to 120 V or 24 V. Dual-voltage primaries are linked for the supply: on a common 240 × 480 V design, H2 to H3 for 480 V, and H1 to H3 plus H2 to H4 for 240 V.
One side of the secondary (X2) is usually grounded, with the fuse in the ungrounded side (X1). Control devices go on the X1 side and the coil connects to X2. A ground fault in the control wiring then blows the fuse instead of starting the motor.
Size a control transformer in volt-amperes (VA). Secondary current = VA ÷ secondary voltage. Coils draw several times their sealed VA while they pull in, so selection tables use inrush VA as well as sealed VA.
Worked example 3: control transformer load. A 120 V control circuit has three starter coils at 20 VA sealed each and four pilot lights at 4 VA each. Sealed load = 3 × 20 + 4 × 4 = 60 + 16 = 76 VA, which is 76 ÷ 120 ≈ 0.63 A. A 100 VA transformer can supply 100 ÷ 120 ≈ 0.83 A, so the steady load fits. Now one coil pulls in at 150 VA while the other two are sealed: momentary load = 150 + 2 × 20 + 16 = 206 VA. That's more than twice the transformer's rating, so check the maker's inrush table. Too small a transformer lets the voltage sag and the contactor chatter.
A variable frequency drive (VFD) rectifies the incoming AC to a DC bus, roughly 650 to 680 V DC on a 480 V drive, and an inverter turns that back into variable-frequency AC by pulse-width modulation. Below base frequency it holds volts per hertz constant, so the motor keeps roughly full torque. Above base frequency the voltage can't rise further, so available torque falls.
- Cooling. A shaft-mounted fan slows with the motor. A standard motor run hard at low speed for long periods can overheat.
- Overvoltage trips while stopping. A fast deceleration makes the motor act as a generator and pump energy into the DC bus. Lengthen the decel time or add dynamic braking.
- Stored energy. The DC bus capacitors stay charged after you switch off. Wait the time on the drive's label, then measure the bus before touching anything. A drive's stop or enable is never an isolation point.
Worked example 4: a motor on a VFD. A 460 V, 60 Hz, 4-pole motor with a 1,755 rpm nameplate runs on a VFD at 36 Hz. Synchronous speed = 120 × 36 ÷ 4 = 1,080 rpm. Constant volts per hertz: 460 ÷ 60 ≈ 7.67 V/Hz, so the drive puts out about 460 × 36 ÷ 60 = 276 V. At the same load torque, the slip in rpm stays roughly what it was at 60 Hz, 1,800 − 1,755 = 45 rpm, so the shaft turns at about 1,080 − 45 = 1,035 rpm.
Reading ladder diagrams and wiring prints
Three kinds of drawing turn up:
- A ladder diagram (schematic or elementary) shows how the control circuit works, one rung at a time, between two rails such as X1 and X2.
- A wiring diagram (connection diagram) shows where devices and terminals physically are and how the wires run between them.
- A one-line diagram shows power distribution, with a single line standing for a multi-conductor circuit.
On a ladder print:
- Contacts are drawn in their normal state: device at rest, circuit de-energized. "Normally open" describes the device, not the machine's running condition.
- Each rung ends in an output (coil, light, solenoid) at the right, with the contacts that control it to its left. Contacts in series are AND; contacts in parallel are OR.
- A coil and its contacts share a label (M, CR1, TR2). On many prints, numbers beside a rung list the rungs where that coil's contacts appear.
- Wire numbers change at every device. Two points with the same wire number are the same electrical point.
| Timer contact | Behavior |
|---|---|
| On-delay, normally open, timed closed | closes after the preset once the coil is energized |
| On-delay, normally closed, timed open | opens after the preset once the coil is energized |
| Off-delay, normally open, timed open | closes at once; opens after the preset once the coil is de-energized |
| Off-delay, normally closed, timed closed | opens at once; recloses after the preset once the coil is de-energized |
Worked example 5: tracing a rung by wire number. A 120 V rung runs, in order: X1, fuse, wire 1, STOP (normally closed), wire 2, START, wire 3, coil M, wire 4, overload contact, X2. The starter won't pull in. Qualified and wearing the right PPE, you put the black lead on X2 and hold START. Wires 1, 2, 3 and 4 all read 120 V.
Read it this way. Current through the coil would drop the full 120 V across it, leaving wire 4 near 0 V. Wire 4 still reads 120 V, so no current is flowing: the path is open between wire 4 and X2. That's the overload contact or its wiring, and across the contact you'd read the full 120 V. Had the coil been open instead, wire 3 would read 120 V and wire 4 would read 0 V. Either way, the voltage disappears just past the open device. If the overload has tripped, find out why before you reset it.
Practice that matches the test
Motor and control questions reward two habits: write the formula before you use it, and follow the current path one device at a time. For signals, sensors and PLCs, see the PLCs, electronics and test instruments guide. For power, transformers and safe isolation, see the AC/DC theory guide. For a full plan, read how to prepare for the Ramsay MultiCrafTest.
The free MultiCrafTest practice test has two questions from each craft area. Our 20 full Ramsay MultiCrafTest practice tests mix 60 original questions across all seven areas, with a worked explanation for every one and your score for each area.
Watch the video lesson
- Motor Control Ladder Diagram Test Questions: Seal-In, STOP and JOG on ExamVanta's YouTube channel
Free to share: you may copy and share this guide unchanged, for non-commercial purposes such as teaching and study, if you credit ExamVanta and link to this page. It's licensed under CC BY-NC-ND 4.0. Material from other sources quoted or shown in it, such as official text or chart excerpts, keeps its own terms.
More Ramsay MultiCrafTest guides
- How to Prepare for the Ramsay MultiCrafTest: A Study Plan
A practical plan for the Ramsay MultiCrafTest: what the seven craft areas cover, how to find your weakest areas, which formulas to know, and how to pace 60 questions.
- MultiCrafTest AC/DC Theory: Three-Phase Power and Safety
AC/DC theory and electrical maintenance for the Ramsay MultiCrafTest: Ohm's law, three-phase power, transformers, voltage drop, grounding, insulation tests and safe work.
- MultiCrafTest Electrical Maintenance: Formulas, Ladder Logic
The electrical side of the Ramsay MultiCrafTest: AC/DC theory, motors and controls, ladder diagrams and PLC signals, with formulas and worked examples.
- MultiCrafTest Hydraulics and Pneumatics: Worked Examples
Hydraulics and pneumatics for the Ramsay MultiCrafTest: force, speed, horsepower and heat, valves, air use and troubleshooting, with worked examples you can check.
- MultiCrafTest Mechanical Maintenance: Formulas and Examples
The mechanical side of the Ramsay MultiCrafTest: hydraulics and pneumatics, welding and rigging, power transmission and pumps, with formulas and worked examples.
- MultiCrafTest PLCs, Electronics and Test Instruments Guide
PLCs, electronics and test instruments for the Ramsay MultiCrafTest: PLC scan and I/O, 4–20 mA scaling, sensors, safe meter use and logic gates, with worked examples.
- MultiCrafTest Power Transmission: Belts, Gears, Bearings
Power transmission and mechanical maintenance for the Ramsay MultiCrafTest: drive ratios, torque, chains, bearing life, lubrication, alignment and bolting, with examples.
- MultiCrafTest Pumps, Piping and Combustion: Worked Examples
Pumps, piping and combustion for the Ramsay MultiCrafTest: head and pressure, pump power, affinity laws, NPSH and cavitation, water hammer, steam traps and burners.
- MultiCrafTest Welding and Rigging: Sling Angles and Welds
Welding and rigging for the Ramsay MultiCrafTest: sling tension, load share, hitch capacity, electrodes, weld defects, heat input and hot work, with worked examples.
- Ramsay MecTest vs MultiCrafTest: Which Test Is Yours?
Ramsay's maintenance tests compared: MultiCrafTest, MecTest, Maintenance Troubleshooter, MultiCraft Aptitude Test and more, by items, level and content.
- Ramsay MultiCrafTest Scores: Norms, Percentiles, Cut Scores
What a Ramsay MultiCrafTest score means: Ramsay's published norms, a score of 40 of 60 against them, percentiles, employer cut scores and retesting.